Case Studies
General Aniline & Film
- Ennis, Texas
General Aniline & Film
Ennis, Texas
Project Name: General Aniline & Film
Location: 202 Cedar Road, Ennis, TX, 75119
Project Type: Office Building
Synopsis: The existing fire pump equipment at General Aniline & Film failed, leaving the office building without adequate fire protection. A temporary fire pump solution was required to maintain compliance and safety while awaiting the installation of a new permanent system.
Details: With the failure of the existing fire pump, the building’s fire protection system was compromised, creating potential risks for employees and operations. Due to the lead time for replacing the permanent pump, an immediate temporary solution was needed to restore fire safety measures and maintain compliance with fire codes.
Solution: By partnering with RentFirePumps.com, a mobile temporary fire pump was delivered and installed, ensuring that the office building remained protected and operational. This solution allowed business operations to continue without disruption while awaiting the installation of a new fire pump. By utilizing a temporary fire pump, General Aniline & Film successfully maintained fire safety compliance, ensuring uninterrupted operations while the permanent pump was being replaced.
Temporary Fire Pump Specifications: Diesel 1,250 GPM @ 114 PSI – FP Controller (110 v) – Jockey Pump – JP Controller – Test Header –Discharge – Pressure relief valve (Dial in the required pressure) – Day Tank – Low Fuel Alarm
440 West Condominiums
- Clearwater, FL
440 West Condominiums
Clearwater, FL
Project Name: 440 West Condominiums
Location: 440 Gulfview Blvd. S, Clearwater, FL 33767
Project Type: Condominiums
Synopsis: Hurricane Helene’s powerful storm surge caused severe flooding in the fire pump equipment rooms of two buildings at 440 West Condominiums. As a result, both fire pumps were rendered inoperable, leaving the property without a functional fire suppression system. An immediate solution was required to restore fire protection and ensure resident safety while long-term repairs and replacements were planned.
Details: Located along Clearwater Beach, 440 West Condominiums faced extensive water damage as storm surge waters breached critical infrastructure. With both fire pumps submerged and inoperable, the risk to residents and property was significant. The condominium management needed a rapid response to reinstate fire suppression capabilities, meeting local safety regulations and ensuring continued occupancy.
Solution: A temporary fire pump system was deployed to provide reliable fire protection while the existing equipment was assessed and replaced. The temporary system was strategically positioned to bypass the damaged infrastructure and deliver the necessary water pressure for the fire suppression system. This allowed for uninterrupted fire safety coverage without displacing residents or disrupting daily operations. By swiftly implementing a temporary fire pump system, 440 West Condominiums was able to maintain compliance with fire safety regulations and protect its residents while permanent repairs were underway. The quick response ensured a seamless transition back to a fully operational fire suppression system without compromising safety.
Temporary Fire Pump Specifications: Diesel 1,000 GPM @ 110 PSI – FP Controller (110 v) – Jockey Pump – JP Controller – Test Header –Discharge – Pressure relief valve (Dial in the required pressure) – Day Tank – Low Fuel Alarm
440 West Condominiums: https://440westcondofl.pilera.com/
Advent Health Hospital
- Ocala, Florida
Advent Health Hospital
Ocala, Florida
Project Name: Advent Health Hospital Ocala
Location: 1500 SW 1st Ave, Ocala, FL 34471
Project Type: Acute Care Community Hospital
Synopsis: Automatic transfer switch failure leaves community hospital exposed to risk of fire protection system failure if power outage occurs.
Details: Advent Health’s Ocala Hospital is a leading provider of acute care for the North-Central Florida region. Upon learning that the automatic transfer switch on the electric fire pump controller failed to operate during routine testing, the Plant Operations Manager was left searching for a solution to ensure that the Hospital, as well as it’s patients and team members would be protected if there was a loss of power during an emergency fire event.
By partnering with RentFirePumps.com a mobile temporary fire pump solution was delivered ensuring that the facility would maintain adequate fire protection coverage until a new fire pump controller with built in automatic transfer switch could be installed.
Solution: RentFirePumps.com delivered and installed a mobile temporary fire pump to provide 1000 GPM to the Hospital’s fire sprinkler system(s) protecting patients, team members, and the building.
Temporary Fire Pump: Diesel 1000 GPM @ 165 PSI – FP Controller (110 v) – Jockey Pump – JP Controller – Test Header –Discharge – Pressure relief valve (Dial in the required pressure) – Day Tank – Low Fuel Alarm
Advent Health Hospital Ocala: https://www.adventhealth.com/hospital/adventhealth-ocala
AHJ & Property Manager Training
- Orlando, Florida
AHJ & Property Manager Training
Orlando, Florida
Project Name: AHJ & Property Manager Training
Location: Orlando Florida
Project Type: Training
Synopsis: RentFirePumps.com provides Fire Pump training for AHJ’s and Property Managers – If your Fire Pump is not operational; NFPA25 considers this a critical impairment and requires a Fire Watch – with our pump room on wheels you can get your Fire Protection system Compliant – No More Fire Watch.
Allegro
- Parkland, Florida
Allegro
Parkland, Florida
Project Name: Allegro
Location: Parkland, FL
Type of Property: 3-Story 187,153 Sq. Ft. Senior Living Facility
Synopsis: Allegro required temporary fire pump. Temporary fire pump successfully installed to avoid additional downtime. Due to water service not conveyed and project in jeopardy of being closed during new construction, RentFirePumps.com installed (2) temporary water holding tanks.
Allegro: https://www.allegroliving.com/communities/parkland-fl?
Bay Pines VA Healthcare System
- Bay Pines, Florida
Bay Pines VA Healthcare System
Bay Pines, Florida
Project Name: Bay Pines VA Healthcare System
Location: 10000 Bay Pines Blvd, Bay Pines FL 33744
Project Type: Veterans Administration Healthcare system
Synopsis: A pre-planned project required a temporary mobile fire pump for a 2-month duration.
Details: The existing fire pump for the building failed and had to be replaced, this project was planned to take up to two months. A temporary mobile fire pump was required to ensure the building would keep active fire protection for the duration of the transition.
Solution: RentFirePumps.com offers a full line of UL-FM listed mobile fire pump units, providing temporary emergency solutions for impairments lasting longer than 24 hours to help avoid costly fire-watch or loss of occupancy.
Temporary Fire Pump Specifications: Diesel-powered 1500 GPM @ 155 PSI, including FP Controller (220v), Jockey Pump, JP Controller, Test Header, Discharge, Pressure Relief Valve (adjustable), Day Tank, and Low Fuel Alarm.
Beacon Centre 5 / Prologis
- Doral, Florida
Beacon Centre 5 / Prologis
Doral, Florida
Project Name: Beacon Centre 5, Prologis
Location:2000 Northwest 84th Avenue, Doral, FL 33172
Project Type: Warehouse
Synopsis: Diesel fire pump engine failure leaves Beacon Centre 5 without fire protection and facing lengthy fire-watch due to extended lead times on replacement equipment.
Details: Beacon Centre 5 experienced diesel pump failure due to engine fire and with the help of their knowledgeable property management and real estate investment firm they connected with Sprinklermatic and were able to get a RentFirePumps.com pump rental to meet their buildings needs to provide an immediate solution.
Solution: A mobile temporary fire pump was mobilized and installed within 24 hours of approval and help from the building electrician to run the proper electric run to the trailer. A full capacity flow test was performed to confirm that the mobile unit was capable of meeting the fire sprinkler system(s) demand.
Temporary Fire Pump: Diesel 1250GPM @125PSI complete with Jockey pump, controllers, test header, high PSI hose and Storz connection, fittings, fuel tank and high pressure rubber jacketed hose.
Beacon Centre 5 / Prologis: https://www.prologis.com/industrial-properties/building/mia00305-prologis-beacon-centre-5
Brickell Key
- Miami, Florida
Brickell Key
Miami, Florida
Project Name: Brickell Key
Location: Miami, FL
Type of Property: Condominium
Synopsis: Temporary fire pump installed for Brickell Key Condominium.
Brickell Key: https://brickellkeymiami.com/
Brooklyn Naval Yard
- Brooklyn, New York
Brooklyn Naval Yard
Brooklyn, New York
Project Name: Brooklyn Naval Yard
Location: 63 Flushing Avenue, Brooklyn, NY 11205
Project Type: Naval Yard
Synopsis: A major building expansion at the Brooklyn Naval Yard required an increase in fire suppression capacity to meet updated safety regulations and operational needs. The existing fire protection system was insufficient to support the additional fire pump demand, necessitating a temporary solution while a permanent upgrade was designed and installed.
Details: As a critical naval facility, maintaining uninterrupted fire protection was essential to ensure the safety of personnel, infrastructure, and high-value assets. With the expansion underway, the increased square footage and structural modifications placed a higher demand on the fire suppression system. To bridge the gap until the new permanent system was fully implemented, a temporary fire pump was deployed to meet compliance standards and maintain operational safety.
Solution: A high-capacity temporary fire pump unit was installed to supplement the existing system, providing the additional pressure and flow rate required for the expanded facility. The integration of this temporary solution ensured continuous fire protection without disrupting ongoing naval operations or construction activities. By implementing this strategic temporary fire pump solution, Brooklyn Naval Yard successfully addressed the increased fire suppression demand, ensuring compliance and safety while awaiting the completion of its upgraded fire protection infrastructure.
Temporary Fire Pump Specifications: Diesel 750 GPM @ 175 PSI – FP Controller (110 v) – Jockey Pump – JP Controller – Test Header –Discharge – Pressure relief valve (Dial in the required pressure) – Day Tank – Low Fuel Alarm
Brooklyn Naval Yard: https://www.brooklynnavyyard.org/
Cargill Dry Corn Ingredients
- Paris, Illinois
Cargill Dry Corn Ingredients
Paris, Illinois
Project Name: Cargill Dry Corn Ingredients
Location: 616 South Jefferson Street, Paris, IL 61944
Project Type: Processing and Storage Facility
Synopsis: Cargill Dry Corn Ingredients faced a significant operational challenge when its existing fire pump system failed, leaving the facility without adequate fire protection. To ensure compliance with fire safety regulations and maintain the security of valuable inventory, an immediate temporary fire pump solution was required.
Details: As a major processing and storage facility for dry corn ingredients, maintaining fire suppression capabilities was critical to safeguarding both personnel and stored goods. The unexpected fire pump failure posed a risk of operational downtime and regulatory non-compliance, making a swift and reliable solution necessary.
Solution: A temporary fire pump system was deployed to provide continuous fire protection while a permanent replacement was sourced and installed. The temporary pump was seamlessly integrated into the facility’s fire suppression infrastructure, ensuring uninterrupted protection for the warehouse, employees, and inventory. This solution allowed operations to continue without disruption while mitigating potential fire hazards. By implementing this temporary fire pump solution, Cargill Dry Corn Ingredients successfully maintained fire protection, ensuring operational continuity and compliance with safety standards while preparing for a long-term system replacement.
Temporary Fire Pump Specifications: Diesel 750 GPM @ 175 PSI – FP Controller (110 v) – Jockey Pump – JP Controller – Test Header –Discharge – Pressure relief valve (Dial in the required pressure) – Day Tank – Low Fuel Alarm
Cargill Dry Corn Ingredients: https://www.cargill.com/food-beverage/na/dry-corn-ingredients
Comar LLC Buena
- Buena New Jersey
Comar LLC Buena
Buena New Jersey
Project Name: Comar LLC,Buena
Location: 1 Comar Place, Buena NJ 08360
Project Type: Medical Supply Manufacturer
Synopsis: The building was scheduled for planned maintenance which would temporarily
disable fire protection.
Details: Customer stated holding tanks were scheduled for cleaning and needed a temporary fire
pump to avoid loss of active fire protection.
Solution: RentFirePumps.com offers a full line of UL-FM listed mobile fire pump units,
providing temporary emergency solutions for impairments lasting longer than 24 hours to help
avoid costly fire-watch or loss of occupancy.
Temporary Fire Pump Specifications: Diesel-powered 1250 GPM @ 114 PSI, including FP
Controller (220v), Jockey Pump, JP Controller, Test Header, Discharge, Pressure Relief Valve
(adjustable), Day Tank, and Low Fuel Alarm.
Comar: https://www.comar.com/
Country Inn & Suites Tampa
- Tampa, Florida
Country Inn & Suites Tampa
Tampa, Florida
Project Name: Country Inn & Suites, Tampa
Location: 4750 North Dale Mabry Highway, Tampa, Florida
Project Type: Hotel & Suites
Synopsis: The existing electric fire pump at Country Inn & Suites failed, leaving the hotel without adequate fire protection. A temporary fire pump solution was required to maintain compliance and safety while awaiting the installation of a new permanent system.
Details: With the failure of the existing electric fire pump, the hotel’s fire protection system was compromised, posing a risk to guests and operations. Given the lead time for replacing the permanent pump, an immediate temporary solution was needed to restore fire safety measures and maintain compliance with fire codes.
Solution: By partnering with RentFirePumps.com, a mobile temporary fire pump was delivered and installed, ensuring that the hotel remained protected and operational. This solution allowed the hotel to continue accommodating guests without disruption while awaiting the installation of a new fire pump. By utilizing a temporary fire pump, Country Inn & Suites successfully maintained fire safety compliance, ensuring uninterrupted operations and guest safety while the permanent pump was being replaced.
Temporary Fire Pump Specifications: Diesel 1,250 GPM @ 114 PSI – FP Controller (110 v) – Jockey Pump – JP Controller – Test Header –Discharge – Pressure relief valve (Dial in the required pressure) – Day Tank – Low Fuel Alarm
Country Inn & Suites: https://www.choicehotels.com/florida/tampa/country-inn-suites-hotels/fld26?mc=llgoxxpx