Sheridan Suites

Project Name: Sheridan Suites

Location: 311 N. University Drive, Plantation, FL 33324

Property Type: 10 Story Hotel

Synopsis: Fire pump located in adjacent garage scheduled for demolition. New fire pump building would not be completed prior to demolition.

Solution: Install a temporary – Diesel Fire Pump

Installation of a Temporary Diesel Fire Pump. Supply water to the pump from an adjacent hydrant. Add a tee and check valve to the existing Fire Department Connection – back feed the FDC from the Temp pump. Electric is provided from house power – a dedicated circuit for the Controller, and control wire to jockey Pump and JP controller. We will test the Fire pump from the test header and roof manifolds.